Item Code: 38623296224

The Siemens RMG88.62C2 is a microcontroller-based burner control designed for automated startup and supervision of single- or multi-stage forced draft gas and oil burners operating in intermittent mode. It ensures safe and efficient operation by managing burner sequences and continuously monitoring flame presence, specifically handling forced draft gas burners via ionization probes or UV detectors with an ancillary unit. Operating on AC 220-240 V and featuring a safety timer of 3 seconds and a pre-purge time of 20 seconds, this C-Series unit is a legacy model now being phased out in favor of the newer CMG88.62D2.
| Parameter | Value |
|---|---|
| Compatible Flame Detectors (Oil) | Photoresistive detectors QRB1B... (for yellow flames) and blue-flame detectors QRC... (for blue flames) |
| Mounting Position | Optional |
| Required Accessories | Plug-in base (needs to be ordered separately) |
| Device Type | Microcontroller-based burner control box, C-Series |
| Mains Voltage | AC 220-240 V |
| Mains Frequency | 50-60 Hz |
| Built-in Fuse | T6.3A |
| Safety Timer (TSA) | 3 seconds |
| Pre-purge Time (t1) | 20 seconds |
| Operating Temperature Range | -5 to +60 °C |
| Weight | Approximately 260 g |
| Compatible Flame Detectors (Gas) | Ionization probe or flame detector QRA... (with ancillary unit AGQ2...A27) |